By using this corrosion inhibitor the build up of sediment deposits and damaging corrosion of water boilers is greatly reduced. Our research and experience recomend to working water at a rate of 0.5 to 1.0 percent of the weight of water in the system. This amounts to 4 up to 8 Ltr corrosion inhibitor in 100 gallons of water.
RXSOL-40-4011-025 is a superior multifunctional, nitrite-based chemical treatment used for the control of corrosion in closed cooling systems and chilled water systems. RXSOL-40-4011-025 is a liquid product containing a combination of ferrous and non-ferrous corrosion inhibitors, a non-carbonate buffer, scale inhibitors, dispersants and a leak detection dye.
The recommended dosage of RXSOL-40-4011-025 is 15.6-23.4 l/m3 of system capacity or 60.6-87 RXSOL-40-4011-025 of system capacity in all systems. Clean up the system if the system becomes contaminated with iron. Maintain 600-750 ppm nitrite as NO2. RXSOL-40-4011-025 is intended for industrial use only. It should not be fed to potable water systems