Of Marine Chemical Solutions
Of Marine Chemical Solutions
Descaling Chemical viscous Compound Suitable for Descaling of Copper tube of Chillers and Condenser of Air Conditioning Plant
30.00Kg.(Liq)
Descaling Chemical viscous Compound Suitable for Descaling of Copper tube of Chillers and Condenser of Air Conditioning Plant. Advanced formulation and Non Corrosive to material Non Polluting and Effective to remove Scale deposited inside Copper tubes. This Compound is Safe to handle also.
Product Technical bulletin
Descaling Chemical viscous Compound Suitable for Descaling of Copper tube of Chillers and Condenser of Air Conditioning Plant. Advanced formulation and Non Corrosive to material Non Polluting and Effective to remove Scale deposited inside Copper tubes. This Compound is Safe to handle also.
RXSOL-41-8865-025 contains powerful dissolving agent for various mineral compounda. Early stage uses of RXSOL-41-8865-025 prohibit scales build up which results tube blockage, or regular cleaning is recommended as well. It is impossible to do a circulating cleaning when the tube is completely blocked.
* Calcium sulfate is easier to be formed when the temperature goes higher.
Descaling Chemical compound Should have following Properties
Odour |
Characteristic smell |
Appearance |
Viscous Liquid, soluble in water |
pH (Neat) |
< 2.0 at 100 % concentration |
Boiling point |
~ 100 °C at 760 mm /Hg |
Vapour pressure |
105.5 at 20 deg C |
Specific gravity (water=1) |
1.20±0.05 |
Freezing point~ |
30 °C at 760 mm/Hg |
Solubility with water at 20 degree C |
100% |
Flammable |
Non combustible |
The most effective method of RXSOL-41-8865-025 is circulation for large systems or components. In the case of small components, the soak method in an immersion bath can be used.
If the equipment to be cleaned is contaminated by oil, grease, sludge or carbonised oil, then pre-cleaning with RXSOL-20-2002-SC or Rxsol-10-1006 is necessary.
RXSOL-41-8865-025 dilute with fresh water as 5-30%, solution depending on scale.Make a circulation system so as to allow the solution to enter through the lowest point and leave through the highest point of the equipment, which is to be descaled.
TIPS for CLEANING
Fill up the whole system with the solution and circulate through a centrifugal pump.
At the initial stages, pH of the solution is generally at 2 to 3 there is increase in the pH of the solution, during reaction.The increase in the pH of the solution during circulation reflects on going reaction. Add more quantity of RXSOL-41-8865-025 and continue circulation, in case of the pH level being 4.5 to 5. If circulation of system shows constant pH 2 to 3 after time confirms the completion of the process of descaling.